HomeMy WebLinkAboutDIV II) CH 1 Water Service: Section 23 - Non-Responsibility of District23-1
SECTION 23 NON-RESPONSIBILITY OF DISTRICT
23.01 INTERRUPTIONS OF WATER SERVICE
District does not guarantee continuous delivery of water
on demand. From time to time it may be necessary for the
District to shut off the flow of water in any of its water
systems. Except in emergencies, such stoppages will not be
made without prior notice to the customers involved. District
shall not assume any responsibility for loss or damages which
may occur due to interruption of water service.
23.02 PRIVATELY-OWNED WATER LINES
The District assumes no responsibility for the delivery
of water through privately-owned pipelines or systems, nor
shall it assume any responsibility for damages resulting from
the operation of any such system even though water may be
received from a district water distribution system.
23.03 WATER PRESSURE REGULATION
A.Customer Responsibility. The District shall
assume no responsibility for water pressure
regulation within a customer's service area. The
customer shall be responsible for providing adequate
safeguard measures for the customer's water system
wherever pressure regulation is necessary.
B.Requirement for Installation in New Construction.
Customers making application for water service for
new construction for residential, commercial or
industrial use shall be required to install an
appropriate pressure regulation device for such
service.
23.04 CROSS-CONNECTIONS AND BACKFLOW DEVICES
State Regulations for Cross-Connections
The California State Water Resources Control Board has
issued regulations related to cross-connections, outlined in
the Cross-Connection Control Policy Handbook, for the purpose
of safeguarding drinking water supplies by preventing backflow
into public water systems.
It is unlawful for any person, firm, or corporation at
any time to make or maintain, or cause to be made or main-
tained, temporarily or permanently, for any period of time
whatsoever, any cross-connection between plumbing pipes or
water fixtures being served with water by the District water
department and any other source of water supply; or to main-
tain any sanitary fixtures or other appurtenances or fixtures
23-2
which, by reason of their construction, may cause or allow
backflow of water or other substances into the water supply
system of the District and/or the service of water pipes or
fixtures of any consumer of the District.
A.Definitions: For a complete listing, see the
California State Water Resources Control Board’s Cross-
Connection Control Policy Handbook.
1.Air-Gap Separation (AG): The term "air-gap
separation" means a physical break between a supply
pipe and a receiving vessel. The air-gap shall be
at least double the diameter of the supply pipe
measured vertically above the top rim of the vessel,
in no case less than one inch.
2.Approved Backflow Prevention Device: The term
"approved backflow prevention device" shall mean
devices which have passed laboratory and field
evaluation tests performed by a recognized testing
organization which has demonstrated their competency
to perform such test to the California Department of
Health Services and the Otay Water District.
3.AWWA Standard: The term "AWWA Standard" means an
official standard developed and approved by the
American Water Works Association (AWWA).
4.Backflow: The term "backflow" shall mean a flow
condition, caused by a differential in pressure that
causes the flow of water or other liquids, gases,
mixtures or substances into the distributing pipes
of a potable supply of water from any source or
sources other than an approved water supply source.
Back-siphonage is one cause of backflow. Back
pressure is the other cause.
5.Cross-Connection: The term "cross-connection" as
used in this Ordinance means any unprotected actual
or potential connection between a potable water
system used to supply water for drinking purposes
and any source or system containing unapproved water
or a substance that is not or cannot be approved as
safe, wholesome, and potable. Bypass arrangements,
jumper connections, removable sections, swivel or
changeover devices, or other devices through which
backflow could occur, shall be considered to be
cross-connections.
6.Double Check Valve Assembly: The term "double check
valve assembly" means an assembly of at least two
independently acting check valves, including tightly
closing shut-off valves, on each side of the check
23-3
valve assembly and test cocks available for testing
the water tightness of each check valve.
7.Reduced Pressure Principle Backflow Prevention
Device (RP): The term "reduced pressure principle
backflow prevention device" means a device
incorporating two or more check valves and an
automatically operating differential relief valve
located between the two check valves, a tightly
closing shut-off valve on each side of the check
valve assembly, and equipped with necessary test
cocks for testing.
8.Reduced Pressure Detection Assembly (RPDA): Same as
RP except as approved for fire services.
9.Service Connection: The term "service connection"
refers to the point of connection of a user's piping
to the Otay Water District facilities.
B.General Provisions
1.Unprotected cross-connections with the public
water supply are prohibited.
2.Whenever backflow protection has been found
necessary, the District will require the water
user to install an approved backflow prevention
device, by and at his/her expense, for continued
services or before a new service will be granted.
3.Wherever backflow protection has been found
necessary on a water supply line entering a water
user's premises, then any and all water supply
lines from the District's mains entering such
premises, buildings, or structures shall be
protected by an approved backflow prevention
device. The type of device to be installed will
be in accordance with the requirements of this
Ordinance.
C.Where Protection is Required
1.Each service connection from the District water
system for supplying water to premises having an
auxiliary water supply shall be protected against
backflow of water from the premises into the
public water system.
23-4
2.Each service connection from the District water
system for supplying water to any premises on
which any substance is handled in such fashion as
may allow its entry into the water system shall
be protected against backflow of the water from
the premises into the public system. This
includes commercial accounts, fire service
accounts, irrigation accounts, multi-family
dwellings, multi-story buildings, complex piping,
and locations where the handling of process
waters and waters originating from the District
water system may be subjected to deterioration in
sanitary quality.
D.Type of Protection Required
1.The type of protection that shall be provided to
prevent backflow into the approved water supply
shall be commensurate to the degree of hazard
that exists on the consumer's premises. The type
of protective device that may be required (listed
in increasing levels of protection) includes:
double check valve backflow prevention
assemblies, reduced pressure principle backflow
prevention assemblies (RP), and an air-gap
separation (AG). The water user may choose a
higher level of protection than that required by
the District. The minimum types of backflow
protection required to protect the approved water
supply at the user's water connection to premises
with varying degrees of hazard are given in
Appendix D of the Cross-Connection Control Policy
Handbook. Situations which are not covered in
Appendix D shall be evaluated on a case-by-case
basis, and the appropriate backflow protection
shall be determined by the District.
E.Approved Backflow Prevention Devices
1.Only lead-free backflow prevention assemblies
which have been approved by the District shall be
acceptable for installation by a water user
connected to the District's potable water system.
2.The District will provide to any affected cus-
tomer, upon their request, a list of approved
backflow prevention devices.
F.Backflow Prevention Device Installation
23-5
1.Backflow prevention devices shall be installed in
a manner prescribed in Article 3 of the Cross-
Connection Control Policy Handbook. Location of
the devices should be as close as practical to
the user's connection. The District shall have
the final authority in determining the required
location of a backflow prevention device.
a.Air-gap Separation (AG) - The air-gap
separation shall be located on the user's
side of, and as close to, the service
connection as is practical. All piping
from the service connection to the
receiving tank shall be above grade and be
entirely visible. No water use shall be
provided from any point between the
service connection and the air-gap separa-
tion. The water inlet piping shall
terminate a distance of at least two (2)
pipe diameters of the supply inlet, but in
no case less than one inch above the
overflow rim of the receiving tank.
b.Reduced Pressure Principle Backflow
Prevention Device (RP) - The approved
reduced pressure principle backflow
prevention device shall be installed on
the user's side of the service connection
at a distance consistent with the
District's Standard Drawings and
Specifications. The device shall be
installed a minimum of twelve inches (12")
but not more than twenty-four inches (24")
above grade, measured from the bottom of
the relief valve and with a minimum of
twelve inches (12") side clearance, and
twenty-four inches (24”) of clearance on
the side of the assembly containing the
test cocks. The device shall be installed
so that it is readily accessible for
maintenance and testing. Water supplied
from any point between the service
connection and the RP device shall be
protected in a manner approved by the
District. Additionally, materials and
installation shall at all times conform to
water agency standards which can be found
at www.sdwas.org.
G.Backflow Prevention Device Testing and Maintenance
23-6
1.The owners of any premises on which, or on
account of which, backflow prevention devices
are installed shall have the devices tested by a
person who has demonstrated their competency in
testing of these devices to the District and has
been approved by the District. Backflow
prevention devices must be tested at least
annually and immediately after installation,
relocation, or repair. The District may require
a more frequent testing schedule if it is
determined to be necessary. No device shall be
placed back in service unless it is functioning
as required. A testing result submission, in a
form acceptable to the District, shall be made
each time a device is tested, relocated, or
repaired. These devices shall be serviced,
overhauled, or replaced whenever they are found
to be defective and all costs of testing,
repair, and maintenance shall be borne by the
water user.
2.Initial testing after installation and subse-
quent retesting shall at all times conform to
water agency standards as outlined in
www.sdwas.org.
3.The District will supply affected water users
with a list of persons acceptable to the
District to test backflow prevention devices.
The District will notify affected customers by
mail when annual testing of a device is needed
and will also supply users with the necessary
testing information to be submitted each time a
device is tested or repaired.
4.Existing double check valves and pressure vacuum
breakers on median strip irrigation areas which
function adequately may remain in place,
however, as the District no longer recognizes
such devices to be commensurate with the degree
of potential hazard, failures of these devices
will necessitate their replacement with a
reduced pressure principal backflow prevention
device (RP).
H.Backflow Prevention Device Removal
1. Written approval must be obtained from the
District before a backflow prevention device is
23-7
removed, relocated, repaired or replaced.
a.Removal: The use of a device may be
discontinued and device removed from
service upon presentation of sufficient
evidence to the District to verify that a
hazard no longer exists or is not likely
to be created in the future.
b.Relocation: A device may be relocated
following confirmation by the District
that the relocation will continue to
provide the required protection and
satisfy installation requirements. A
retest will be required following the
relocation of the device.
c.Repair: A device may be removed for
repair, provided the water use is either
discontinued until repair is completed and
the device is returned to service, or the
service connection is equipped with other
backflow protection approved by the
District. A retest will be required
following the repair of the device.
d.Replacement: A device may be removed and
replaced provided the water use is
discontinued until the replacement device
is installed and tested. All replacement
devices must be approved by the District
and must be commensurate with the degree
of hazard involved.
I. User Supervisor
1.At each premise where it is necessary, in the
opinion of the District, a user supervisor shall
be designated by and at the expense of the water
user. This user supervisor shall be responsible
for the monitoring of the backflow prevention
devices and for avoidance of cross-connections.
In the event of contamination or pollution of
the drinking water system due to a cross-
connection on the premises, the District shall
be promptly notified by the user supervisor so
appropriate measures may be taken to overcome
the contamination. The water user shall inform
the District of the user supervisor's required
23-8
information on an annual basis or whenever a
change occurs.
J. Administrative Procedures
Water System Survey
1.The District shall review all requests for new
services to determine if backflow protection is
needed. Plans and specifications must be
submitted to the District upon request for
review of possible cross-connection hazards as a
condition of service for new service
connections. If it is determined that a
backflow prevention device is necessary to
protect the public water system, the required
device must be installed before service will be
activated.
2.The District may require an on premise
inspection to evaluate cross-connection hazards.
The District will transmit a written notice
requesting an inspection appointment to each
affected water user. Any customer who cannot or
will not allow an on premise inspection of their
piping system shall be required to install the
backflow prevention device the District
considers necessary.
3.The District may, at its discretion, require a
reinspection for cross-connection hazards of
any premise to which it serves water. The
District will transmit a written notice
requesting an inspection appointment to each
affected water user. Any customer who cannot
or will not allow an on premise inspection of
their piping system shall be required to
install the backflow prevention device the
District considers necessary.
K.Customer Notification - Device Installation and/or
Repair (Corrective Action)
1.The District will notify the water user of the
survey findings, listing corrective action to
be taken if required. A period of 30 days will
be given to complete all corrective action
required including installation of backflow
prevention devices.
23-9
2.A second notice will be sent to each water user
who does not take the required corrective
action prescribed in the first notice within
the 30 day period allowed. The second notice
will give the water user a 14 day period to
take the required corrective action and will
generate the assessment of a fee in accordance
with Appendix A. If no action is taken within
the 14 day period, the District may terminate
water service to the affected water user until
the required corrective actions are taken.
3.A third and final notice will be sent to each
water user who fails to take the requisite
corrective action detailed in the second notice
within the 14 day period allowed. The third
notice will indicate the date of service
termination and will generate the assessment of
a fee in accordance with Appendix A.
4.Only passing test results from a certified and
District-approved tester/installer received
electronically through the SwiftComply tester’s
portal within the allotted time period will
constitute compliance with the above require-
ments.
L. Customer Notification - Testing
1.The District will notify each affected water
user when it is time for the backflow preven-
tion device installed on their service
connections to be tested. This written notice
shall give the water user 60 days to have the
device tested and will supply the water user
with the necessary testing information to be
used when submitting testing results to the
District.
2.A second notice shall be sent to each water
user who does not have their backflow preven-
tion device tested as prescribed in the first
notice within the 60-day period allowed. The
second notice will give the water user an
additional 14 days to have their backflow
prevention device tested and will generate the
assessment of a fee in accordance with Appendix
A of this Ordinance. If no action is taken
23-10
within the 14-day period, the District may
terminate water service to the affected water
user until the subject device is tested.
3.A third and final notice will be sent to each
water user who fails to have their backflow
prevention device(s) tested as required in the
second notice within the 14-day period allowed.
The third notice will indicate the date of
service termination and will generate the
assessment of a fee in accordance with Appendix
A of this Ordinance.
4.Submittal of passing test results by a District
approved tester, through the SwiftComply
portal, within the allotted time period will
constitute compliance with the above
requirements.
M. Water Service Termination
A.General
When the District encounters water uses that rep-
resent a clear and immediate hazard to the potable
water supply that cannot be immediately abated, the
District shall institute the procedure for
discontinuing the District water service. A
reconnection fee will be assessed in accordance with
Appendix A.
B.Basis for Termination
Conditions or water uses that create a basis for
water service termination shall include, but are not
limited to the following items:
1.Refusal to install a required backflow pre-
vention device;
2.Refusal to test a backflow prevention device;
3.Refusal to repair a faulty backflow prevention
device;
4.Refusal to replace a faulty backflow prevention
device;
5.Direct or indirect connection between the
public water system and a sewer line;
23-11
6.Unprotected direct or indirect connection
between the public water system and a system or
equipment containing contaminants;
7.Unprotected direct or indirect connection
between the public water system and an auxil-
iary water system; and/or
8.Any situation which presents an immediate
health hazard to the public water system.
Additional remedies for failure to comply with cross-
connection requirements are referenced in Section 72 of the
Code of Ordinances and may be prosecuted as set forth in
Section 73.01 of this Code.
N.Water Service Termination Procedures
The District has absolute discretion to determine
the corrective action required and referenced in
Sections 72 and 73 of this Code.
1.For conditions 1, 2, 3, or 4, the District will
terminate service to a customer's premise after
2 written notices have been sent specifying the
corrective action needed and the time period in
which it must be done. If no action is taken
within the allowed time period water service
may be terminated.
2.For conditions 4, 5, 6, 7, or 8, the District
will take the following steps:
a.Make reasonable effort to advise the water
user of intent to terminate water service;
b.Terminate water supply and lock service
valve. The water service will remain
inactive until correction of violations
has been approved by the District.
O. Requirements for addition to or renewal on the Otay
Water District list of approved backflow prevention
device testers
A.Each applicant desiring initial addition to or
annual renewal on the District’s List of
Approved Backflow Prevention Device Testers
shall submit a fee in accordance with Appendix
A. Fees must be made in an acceptable form of
23-12
payment to the District. Along with the fee, a
current address and phone number must be
furnished. Those applicants not meeting all
qualifications specified herein will have
current fees returned.
B.Applicants shall hold a valid and current
certification from the American Water Works
Association (AWWA) California Nevada Section,
American Backflow Prevention Association
(ABPA), American Society of Sanitary
Engineering (ASSE), University of Southern
California Test Procedures (current edition) or
from a certification program recognized by the
San Diego County Health Department. Evidence
of said certification shall be furnished to the
District at the time of application, at the
time of renewal, and at any time the District
requests verification. Certification alone
does not constitute District approval.
C.Each applicant shall furnish evidence to show
the availability of the necessary tools and
equipment to properly test and/or repair such
devices. Test kits shall be recalibrated
annually and evidence of this shall also be
provided with both the initial application and
subsequent renewals.
D.The tester shall be solely responsible for the
competency and accuracy of all tests and
reports prepared and submitted to the District.
The list of approved testers will be furnished
upon request to any District customer requiring
such service.
The testers listed will remain listed for a
period of one year at which time they are
subject to application for renewal. At the
beginning of each year a grace period not to
exceed ninety (90) days will be allowed for
this process. Failure to renew within the
grace period will constitute removal from the
list. The District reserves the authority to
revoke, suspend, or remove any tester from the
list of authorized testers for improper
conduct, testing, repairs, and/or reporting.
23-13
FEES
A.A second notice for required corrective action
will result in a service fee, per backflow
device as outlined in Appendix A.
B.A third notice (termination of service notice)
will result in a service fee per backflow
device followed by the assessment of a
reconnection fee if such action is required as
outlined in Appendix A.
C.A reconnection fee per service is required for
service to be resumed as outlined in Appendix
A.
D.Applicants for addition to the list of approved
backflow prevention device testers in the Otay
Water District will submit an initial filing
fee and an annual renewal fee, as outlined in
Appendix A.
23.05 WATER SERVICE FOR STEAM BOILERS
Customers using District water to supply steam boilers
are required to provide adequate storage of water for boiler
use for a minimum period of 12 hours.
23.06 ELECTRICAL GROUND CONNECTIONS
The connection of electrical ground wire to water pipes
is prohibited. The District shall assume no responsibility
for any loss or damage resulting from such a connection.